GÜVENİŞ Voltage regulators are the machines that provide the constant voltage that you need by correcting the falling and rising of the mains voltage in the internal structure.
Our DVR-M3 Galata Series voltage regulators operate fully automatically for voltage regulation without any user intervention.
Once the regulators are switched on, your mains voltage is continuously measured and the necessary up / down operations are performed automatically, giving your system the constant voltage required for a healthy operation.
Servo regulators consist of variac, servo motor which controls variac, electronic multimeter card which controls this motor and booster transformer.
The start torque can quickly correct even very small voltage changes thanks to the high DC servo motor and the control system that can respond quickly to voltage changes.
When the regulation is completed, the servo motor is de-energized with the aid of the electronic braking circuit. It has high efficiency.
Pollution, parasitic, etc. at output voltage. do not corrupt.
You can safely use any area with regular electricity needs without any problems.
The DVR-M3 Regulator provides the following:
•Protection of the user from negative voltages.
•Protection of the user and the device from excessive current.
•Undisturbed pure sinus voltage regulation.
•Long-term overload protection and short-term protection.
•AC voltage balancing with extremely high accuracy.
•Run smoothly on all loads from 0% to 100%.
•Manual transfer to bypass regime without regulating.
•Display all values against the probabilities in the bypass regime.
•Record mains input voltage limits and load current values.
•Static, not gradual, dynamically correct output voltage too quickly without user notice.
•When protections are activated, record the number of protection trips and the reason for each parameter separately.
TECHNICAL SPECIFICATIONS | |||||
MODEL: GALATA SERIES DVR-M3 | M3-60 | M3-75 | M3-100 | M3-120 | M3-150 |
Power kVA | 60 | 75 | 100 | 120 | 150 |
INPUT | |||||
Input Voltage Correction Range | 190-415 / 275-450 / 310/485 VAC | ||||
Input Voltage Operating Range | >155v…490v< | ||||
Operating Frequency | >47.....64 < | ||||
Input Protection | Overcurrent. Low and High Voltage Protection (Optional) | ||||
OUTPUT | |||||
Output Voltage | >380v…415v< +/- %0,4 | ||||
Overload | 10 SECOND % 200 load | ||||
Correction Speed / Recovery Speed | - 90 Volt / S (150-250VAC the range) | ||||
Output waveform | Pure Sine | ||||
Output protection | Overcurrent. Low and High Voltage Protection (Optional) | ||||
Output protection at low voltage | 337V on - 303V off | ||||
Output protection at high voltage | 424v on ... 433 off | ||||
OPERATING PRINCIPLES | |||||
Servo Motor - Microprocessor - Dynamic Servo | |||||
GENERAL | |||||
Cooling | Natural Air /Smart fan system (Thermostat) (optional) | ||||
Measurement and imaging | Input and Output Voltage Led Display / Input, Output Voltage and Ampere Led Display MULTIMETER | ||||
Continuous operating time at full load | 0..105%. | ||||
Continuous load <105% | < 7 /24 | ||||
Efficiency under load. | >96% | ||||
Mechanical By-pass | Manual control network / 1-0-2 Pako Switch / Remote Switch / Lock key On / Off | ||||
Protection Class | IP20 and Other Options | ||||
ENVIRONMENTAL | |||||
Storage temperature | О> -25 °С <+ 60°С | ||||
Ambient temperature +25 ° C Relative Humidity. | < 96 % | ||||
Operating height | <3000 м 3 km | ||||
Protection Class | IP 21 |